氯瓶基本知识全文
氯瓶维护保养及使用方法前 言为了加强企业危险化学品的安全管理和安全操作及使用,贯彻落实《中华人民全法》《危险化学品安全管理条例》等一系列法律、法规和规定,确保安全生产我们结合操作实践编写了这本安全培训教材,仅供有关管理人员和工作人员参考本教材以法律、法规和规定为基础,以液氯钢瓶为主线,以自来水行业水消毒为容,作了基础知识,实际操作等方面的介绍,从第一章至第四章围绕液氯、液氨为基础容进行了展开,第五章,以氯氨钢瓶在使用中常见故障及排除方法进行了描述另外介绍了液氯的替代产品——次氯酸钠的应用附录中,列出了危险化学品培训考试题选本教材在编写过程中得到了京水集团党委、工会和安全保卫部的大力支持帮助和指导,在此表示衷心的感由于准备时间较匆忙,水平也很有限,错误之处在所难免,望读者在使用中提出宝贵意见 编者 2003、7目 录第一章 危险化学品的容简介·························<1>一、危险化学品的畴和定义····································· <1>二、危险化学品的有关规定································································· <1>三、自来水行业常用的危险化学品························································<2>四、液氯的性质······················································································· <2>五、氯气的用途····················································································· <5>六、氯气的制作····················································································· <6>七、氯气的消毒原理············································································ <7>第二章 液氯与温度、体积、压力等的相互关系············· <8>一、 液氯与压力的关系········································ <8>二、 气体、液体之间的关系··································· <8>三、 瓶均为气态氯时的重量与压力的关系·················· <10>四、 瓶装液体的危险特性·········································· <11>第三章 氯气钢瓶的基本知识···································· <15>一、 气瓶的分类··············································· <15>二、 气瓶的结构及各部用途······································ <15>三、 焊接瓶的结构及各部用途····························· <16>四、 气瓶的检验··········································· <18>五、 气瓶检验工序及注意事项································· <19>第四章 液氯的安全使用、保管、运输······················· <21>一、 安全使用、仓储保管································· <21>二、 运输,有关法规、规定、标准、规则·················· <21>三、 液氯、液氨的运输·········································· <22>四、 漏氯、漏氨的紧急处理 〔23〕五、准备工作和快速抢修··································································· <23>六、人员救护···················································································· <23>七、防氯合剂配方················································································ <23>八、钢瓶在使用中常见故障及排除方法·········································<24>九、故障氯瓶检修工作平台·····························································<25>第五章来水亭牌消毒液〔次氯酸钠〕·················································<28>一、概况·························································<28>二、消毒液生产的依据和标准································<30>三、设备安装要求············································· <31>附录:1、危险化学品培训考试题库························· <33>第一章 液氯的基本知识 危险化学品的概念:化学品中具有易燃、易爆、毒害、放射性等危险特性,在生产、储存、运输、使用和废弃物处置等过程中容易造成人身伤亡、财产毁损、污染环境的均属危险化学品。
170号公约: 我国是国际劳工组织成员国,全国人大八届十次会议批准,我国承认并实施《170号公约》,九四年十月生效 为了加强化学危险品的有效地预防和控制其危害,170公约就化学品的鉴别与分类、登记注册、加贴安全标签、提供说明书给用户、和企业的责任义务、工人的权利和义务、等等要求各成员国建立化学事故控制措施,建立相应制度,加强管理公约的宗旨是要求政府主管当局、雇主组织、工人组织,共同协商努力,采取措施,保护员工免受化学品危害的影响,有助于公众和环境保护安全生产法:20XX6月29日江泽席签署了《中华人民全生产法》,20XX11月1日起施行 安全法是一部综合性安全生产的大法,共七章九十七条,从生产经营单位的安全生产保障到从业人员的权利和义务,从监督管理到生产安全事故的应急处理、法律责任,全面地规了安全生产的管理行为特别值得注意的是在《安全生产法》中对"危险化学品安全管理条例"给予专项明确,充分体现了国家对危险物品安全管理的高度重视危险化学品安全管理条例: 20XX1月26日国务院第334号令颁布了《危险化学品安全管理条例》从20XX3月15日施行条例共分七章七十四条 特点如下: 1、管理部门职责明确。
2、明确危险化学品的分类管辖围〔八大类〕 3、对危险化学品实施全过程的管理 4、明确了一些重要的新规定 与危险化学品有关的法律主要有: 中华人民国劳动法; 中华人民国消防法; 中华人民国职业病防治法; 中华人民国环境保护法; 中华人民国水污染环境防治法; 中华人民国大气污染防治法; 中华人民国海洋环境保护法; 中华人民国固体废物污染环境防治法; 中华人民全生产法 危险化学品的分类: 第一类:爆炸品; 第二类:压缩气体和液化气体; 第三类:易燃液体; 第四类:易燃固体、自燃物品和遇湿易燃物品; 第五类:氧化剂和有机过氧化物; 第六类:有毒品; 第七类:放射性物品; 第八类:腐蚀品 自来水行业使用的消毒材料如下:1. 液氯、液氨是属于危险化学品中第二类液化气体2. 高锰酸钾是属于危险化学品中第五类氧化剂和有机过氧化物下面围绕液氯的基本知识展开 一、安全使用、仓储保管: 储存是指产品在离开生产领域而尚未进入消费领域之前,在流通过程中形成的一种停留不论在生产、经营、储存、使用危险化学品的企业都存在危险化学品的储存问题 《危险化学品安全管理条例》在第二章中对危险化学品的生产、储存和使用的安全管理作了规定,并明确了对危险化学品储存实行审批权制度。
审批条件如下:1. 有符合国家标准的生产工艺、设备或者储存方式、设施;2. 工厂、仓库的周围防护距离符合国家标准或者国家有关规定;3. 有符合生产或者储存需要的管理人员、技术人员;4. 有健全的安全管理制度;5. 符合法律、法规规定和国家标准要求的其他条件; 建筑物:《常用化学危险品贮存通则》〔GB 15603-1995〕中对储存场所也有明确的规定,其耐火等级、层数占地面积防火间距,应符合《建筑设计防火规》〔GBJ 16-20XX版〕的要求 《条例》第二十二条规定:危险化学品出入库,必须进行核查登记库存危险化学品应当定期检查二、 液氯的性质: 氯是一种黄绿色的气体在标准状态下,比空气重2.5倍,有特殊强烈的刺鼻臭味,在常温常压下是气体在常温下20—25 ℃时只要加6—8个大气压就会变成液体而当温度超过144℃时任何压力都不能使气体液化了一般都有采用降温方法,即:常压下温度降至-35℃—— -40℃时气体就液化了,降温较为方便,所以都采用降温方法而不用加压方法 氯气不能燃烧,干燥的氯活动性很小,对金属材料腐蚀很弱,但若遇水或潮湿,就会变成活动性很强的物质对很多金属具有腐蚀性,如:遇水生成盐酸及次氯酸,盐酸对钢瓶有很大的腐蚀性,直接影响容器的使用年限。
因此,液氯的纯度必须严格控制,不得超出化工部标准,即:氯〔体积〕%≥ 99.5,水分含量 % ≤0.06〔按重量〕 氯是一种窒息性毒气,对人类及生物都有危害性,甚至使生命遭受死亡因此使用氯气时应严格注意安全操作 氯气及液氯都不导电,氯气的导热度亦很差,约为空气导热的三分之一氯气很少溶解于水中,从溶解度曲线中〔图1〕可以看到,温度在10℃时,纯水中的最大溶解度仅为1%,温度逐渐上升,溶解度逐渐降低到100℃时,水中就完全不能溶解了在100℃以下,氯和水结合成黄色晶体的水化物〔CL28H2O〕叫氯水,这种现象,有时将造成操作和使用上的困难图1 氯气温度和溶解度的关系曲线 液体氯通常叫液氯是琥珀色的油状液体液氯在常温下比水重1.5倍,液氯的压缩系数在100个大气压以每升气压为0.118%〔溶积〕是液体元素中最大的一个液氯在常温下,压力减小时很快挥发成气体,并吸收大量的热每公斤液氯挥发为氯气时需要吸收67大卡的热量,如果周围热量不够时,就会在容器表面结霜,这样就会阻碍液氯挥发我们学习《常用化学危险品贮存通则》就了解到,从建筑学角度应注意到:设计通风,防火,层数1、通风:排风扇或抽风机的安装必须是在库房、加药间或车间的下方向,依据是氯气比空气重,液体氯挥发成气体,在空间下部聚集。
室安装氯气吸收设备,加以回收利用保护环境不遭破坏或抢修,加速排除氯气,必须严格遵守规,正确安装设施才能起到实效某例:市自来水集团第二水厂,在九十年代初,研制安装氯气回收装置,利用碱液中合氯气,经过反复试验结果如下:将一个0.5吨液氯重瓶放置加药间外,连通管线至封闭的加药间室中心,氯气喷入一个铁盘,铁盘下连接一组暖气进行加热加速液氯气化其结果得到人眼直观的难以想向的效果和最真实可靠的数据,大量的液体氯通过管线流入室,人们通过玻璃窗口看到黄绿色的液体迅速气化,从地面逐步上升就像乖坐飞机向下看白云只不过不是白色的,上面氯气稀薄,接近地面浓厚,在几分钟后充满整个空间停止放氯,但不断地利用抽风机抽氯气,计算时间放氯10分钟,阀门在快速全部打开,常温下,放出170㎏,平均每分钟17㎏20分钟后,工作人员头戴防毒面具进入加药间,取出铁盘到室外,惊奇地发现铁盘中心,仍有一个碗口大的冰坨,随后迅速融化说明:(1) 氯气比空气重,排风设施应装在下部位2) 液氯钢瓶阀门全部迅速打开,常温下每分钟平均排放量是17㎏3) 液氯气化过程需要大量的热量,所以造成使用中,钢瓶表面结冰2、防火:中华人民国消防法1998年4月29日,九届全国人大通过,同年9月1日实起起行。
市人民政府令,1990年第27号,《市建设工程防火设计管理暂行规定》自同年9月1日起施行《市自来水集团治安保卫、消防安全工作制度》中对要害单位、部位安全保卫工作管理标准,都有严格的规定化学危险品的仓储和使用消防法和市都有明确的规定,必须严格执行,在这里不再讨论3、 层数: 液氯重瓶或称满瓶码放应单层,空瓶可三层运输中必须严格执行规程某化工厂,码放空瓶为了减少占地面积,五层码放,因木楔不紧,滑垛,造成有惊无险法律、法规和操作规程往往都是血的教训换来的一个工厂运输液氨空瓶,为了多运码放三层,因紧固绳振松,转弯时钢瓶因离心力作用,抛出将路边小树砸倒严格按照规程办事是安全生产的前提氯气的性质序号名称数 据1分子式CL22原子量35.4533分子量70.9064重度标准气体状态下3.214Kg/m35沸点大气压下液氯沸点-33.9℃,也有-34.05℃或-34.6℃6熔点大气压下固态熔点-100.5℃7临界常数温度tc=144℃压力Pc=76.1大气压 密度c=0.573kg/L8气化热4.878千卡/克分子〔34.1℃〕9熔融热1.531千卡/克分子〔-101.0℃〕10比热气体CP=0.115卡/克℃〔15℃〕CV=0.085卡/克℃液体CP=0.2262卡/克℃〔-80—+30℃〕11导热系数气体6.7×10-3千卡/米、小时、℃液体0.0115-0.0144千卡/米、小时、℃12膨胀系数平均为0.00383613压缩系数1-76大气压间平均为0.00020214溶解度0℃1个大气压下100克水能溶解1.462克15溶解热5.28千卡/克分子16粘度气体0℃ 0.0123厘泊液体0℃ 0.385厘泊17扩散系数0℃1个大气压下空气中0.108厘米2/秒20℃在水中,1.22×10-5厘米2/秒18水化物温度小于9.6℃与水生成CL26H2O水化物,生成热1.836千卡/克分子氯气三、 氯气的用途: 氯气的用途很广泛,如: 〔1〕消毒杀菌:自来水,游泳池用水的消毒。
目前我公司就用氯气杀菌消毒 〔2〕漂白:如纸浆及棉织物的漂白 〔3〕制造无机化合物如:制造漂白粉,氯化亚锡〔还原剂〕,氯化银〔照相用〕合成盐酸等 〔4〕制造有机化合物如:工业药品,聚氯乙稀<塑料>,医药品,农药〔六六六,DDT〕等溶剂再如:橡胶,油脂工业用的四氯化碳,人造丝工业用的氯乙炔,氯乙醇,冷冻剂和氯甲烷氯乙烷二氯甲烷等 〔5〕液氯的毒性: 液氯虽然用途很广,但它的毒性很大,如果使用不当,液氯溢出则带来很严重的危害氯对人的呼吸道和皮肤以及人体其它器官伤害很大氯气与皮肤面部接触,轻者使皮肤干燥,眼睛流泪,重者冻伤,烧伤,吸入氯气后,会引起气管炎,甚至引起肺水肿,以至于血浓度增加,呼吸变慢,心力衰竭而死 表2为氯气不同浓度对人体的毒害性的影响氯气浓度对人体的毒害性〔表2〕毫克/升毫克/米3症 状2.5900立即死亡0.1-0.1535-501/2-1小时死亡〔或一定时间死亡〕0.013.5可以忍耐1/2-1小时0.0010.35可长时间0.003-0.0060.1-0.2可忍耐6小时而无甚显著症状 在空气中只要含有3.5%就可嗅到所以防毒面具最好连眼睛都罩住表3列举氯气对人体危害的浓度。
这是从实践中而得来的一个估计数值事实上要随个人的体质,抵抗力以及氯气接触时间等因素而有不同〔见表3〕氯气对人本影响的浓度〔表3〕危 害 情 况浓 度空气中能察觉气味者最少有百万分之3.5能使咽喉刺痛者最少有百万分之15能引起咳嗽者最少有百万分之30经数小时方能感觉者最少有百万分之1呼吸30分钟即有危险者百万分之40-60呼吸几次即死亡百万分之1000由于氯气的刺激气味很容易辨别,所以在空气中含有少量的氯,人们就能觉察,一经嗅到氯味,就应立即采取措施四、氯气的制作: 制作氯气的原料为食盐、电解食盐水制作黄绿色气体气态在一定压力、一定温度的条件下可以变为液态,上面我们已谈过,把气态加压6-8大气压可变液态,但在工艺上较费事采用降低温度较容易温度降至-35℃以下气态逐渐液化了五、氯气的消毒原理:水中细菌有一些是能致病的为了预防水传染性传染病的发生,对饮用水应该进行消毒国家《生活饮用水卫生标准》中规定,集中式供水,除应根据需要具备必要的净化处理设备外,不论其水源是地表水或地下水,均应有消毒设施送出水接触30分钟后,游离性余氯不低于0.30mg/L集中式供水出厂水应符合上述要求外,管网末梢口余氯量应达到0.03-0.05毫克升,这是掌握对饮用水投加量的依据。
在水入氯气或其它含有效氯的化合物〔漂白粉或其它次氯酸钠〕后进行消毒其消毒原理说法不一,一般有两种论点: 1、氯加入水中后,产生一系列化学变化,其水解反应如下:Cl2+H2OHOCL+H2+CL-反应中,生成的次氯酸很不稳定,极易分解成氯化氢与游离氧HOCL ⇌ HCL+ [O] 上式中游离出来的原子氧[O],又叫初生氧,氧化作用很强,能氧化水中的微生物和细菌,致使这些微生物和细菌的生命活动停止,这是一种比较老的消毒原理的论点 还应说明,除了游离氧具有氧化作用外,氯气本身也能直接消灭细菌2、 氯加入水中后,首先很快地水解,产生次氯酸HOCL,其反应式如下:Cl2+H2O⇌HOCL+H++CL-次氯酸是一种弱电解质,它按下式离解成H+和OCL-HOCL+H++OCL-对于消毒机理最近认为,次氯酸HOCL起主要的消毒作用众所周知,细菌表面带有负电荷,离子状态的次氯酸根OCL-也带负电荷,由于同性电斥力,而很难靠近细菌表面,因此消毒效果很差,次氯酸HOCL是分子量很小的中性分子,只有这才能很快地扩散到细菌表面,并透过细菌的细胞壁和细胞部的酶发生作用,从而破坏细菌的某些酶的系统,最后导致细菌的死亡起到杀菌作用。
在一定条件下,加氯消毒的效果视次氯酸HOCL的多少而定HOCL的多少最重要的因素是取决于被消毒水的PH值,PH值越低,生成次氯酸越多,消毒效果越好;PH值越高生成的次氯酸越少,消毒效果越差当然,氯消毒效果的好坏还有许多因素,如加氯量,氯与水的混合条件接触时间,水的温度和浊度也影响消毒效果我公司各水厂是用氯消毒,用氨去味,氯氨比为3:1至4:1效果较好,我们认为这是一种可靠的消毒方法之一第二章 液氯与温度、体积、压力等的相互关系 一、液氯与压力的关系压力是某一物体垂直均匀作用它一物体单位面积上的力的量度,我们称之为压力液氯离不开压力,液氯与温度压力的关系十分密切液氯随着温度的升高或降低,它的液压都会发生变化随着温度的升高压力就要加大,温度下降压力也就下降,温度与钢瓶的压力〔表压〕的关系如下:温度与瓶压力〔表压〕的关系温度〔℃〕-34.5-20-10010饱和蒸汽压〔Kg/cm2〕00.81.82.74温度〔℃〕2030406080饱和蒸汽压〔kg/cm2〕5.77.510.216.525.5 液氯比氯气重得多,例如:在0℃时瓶为2.7在气压时瓶一升氯气到12.8克,一升液氯重为1468克。
所以瓶氯气在上部,液氯在下部二、 气、液氯的P—U—T关系 液体从形态上看,它具有自由的界面,只能占有空间的某一部分而气态没有自由界面,能够均匀地充满所给予它的整个空间从分子结构来讲,液体分子很密集,并具有相互移动位置的趋势而气体分子则比较松散,且处于无规则的运动状态所以液体密度远比气体密度大这就产生了不同于气体的引力增大,所以液体分子不像气体分子容易自由扩散我们从〔表4〕中就可以看到,气、液态在钢瓶中所占体积也在变化由于液体分子密集,当分子间距离缩短到一定程度时,分子引力转为斥力,所以液体不像气体那样容易压缩这是实验所证实的客观事实由于液体分子密集,当分子受热而加速运动时,分子间碰撞频繁,以至分子斥力胜过引力而使体积比较容易膨胀尽管液体每〔0℃〕的膨胀绝对量很小,但相对于它本身就更小的压缩量就显得很大,这就是液体在容下受热会造成压力急剧增加的主要原因液氯与温度、比容、比重关系表〔表4〕温度〔℃〕压力〔P〕比容比重-301.210.6461.5468-251.490.6521.5342-201.810.6571.5216-152.170.6631.5088-102.60.6680.4957-53.080.6751.482303.640.6811.468554.250.6871.4545104.960.6941.4402155.690.7071.425206.750.1091.4108257.490.7161.3955308.600.7251.3799359.480.7331.36404011.140.7421.34774512.520.7511.33115014.140.7611.31415515.340.7711.29676017.590.7821.27896519.490.7931.26077021.580.8051.24147523.840.8181.22288026.240.8311.2028氯瓶总氯量%气态氯占容积的%0℃ 2.7大气压时20℃ 5.6大气压时40℃ 10.2大气压时100161279025211680333026704238366050474450585655406765643076757420848484109394952.81001.71001100 温度与氯瓶液氯所占的容积关系温度〔℃〕-20-1001020液氯占容积的%8283.58586.588.5温度〔℃〕3040506070液氯占容积的%90.592.59597.5101三、 瓶均为气态氯时的重量与压力的关系: 上面我们谈了气、液态的关系,在这时我们把气态与重量和压力的关系加以说明,我们可以从下列表中看到:瓶均为气态氯时的重量%比瓶压力〔表压〕0℃20℃40℃1002.75.610.2902.359.28024.38701.63.76.8601.23.15.8500.92.44.6400.61.73.5300.212.5200.31.31400.780 瓶均为气态时的重量即液氯刚刚消失,瓶100%的容积均为氯气。
在0℃使用时为原来液氯装入量的1% 在20℃使用时为原为液气装入量的1.7% 在40℃使用时为原为液气装入量的2.8%例如:盛装500公斤氯瓶在40℃使用时,当使用到剩14公斤时,瓶100%容积,均匀气态氯继续使用到剩7公斤时,压力为4.6kg/cm2,当使用到还剩4.2公斤时,压力为2.5kg/cm2,当使用到还剩2.4公斤时,压力为1kg/cm2四、瓶装液体的危险特性关于瓶装液体的危险特性涉及围很广就气体的可燃性来说,应从化学、动力学、爆炸物理学的角度去讨论其燃烧爆炸原理和过程就气体的毒性而言,可以从毒理学和生物学角度去探讨其毒害机理所谓瓶装气体的危险特性—易燃、易爆、腐蚀、有毒以及可能发生分解氧化聚合倾向等等并不是气体装瓶后才有,也不是所有瓶装气体共有的现象瓶装气体独具的危险性,仅仅在于气瓶是移动式受压容器,流动围很广,使用条件无常,因而在客观上比固定式储存容器更难于管理,发生事故的可能性较大液化气体在运输,保管,使用发生泄露时,如一公斤液氯散发出来要扩大到450倍气态因具毒性液化气体泄露而酿成的灾害性事故不少由此可见,掌握液氯超装的危险性要引起重视是十分必要的根据"气瓶安全监察规程"规定的液化气体充装系数,正常充装液氯每升只允许1.21kg/L。
0.5t钢瓶的容积400升,在这样的充装下,瓶的温度不超过60℃,瓶的压力是按照饱和蒸汽压变化的,而当温度上升至68℃时,易熔合金已熔化漏气,因此在正常充气的情况下是安全的但违章操作或因其它原因造成超量包装时,则增大了充填系数由于温度上升液体比重减小而使蒸汽区缩小,超装量越大,它在很低的温度下就会充满,此后,温度稍微升高,则会因液体膨胀系数大于压缩系数,而使压力急剧增加,使钢瓶屈服〔屈服点压力在85-90kg/cm2〕发生显著变形以至发生爆炸 举例说明: 液氯充装系数为1.21kg/L 60℃时液氯的比重1.2789钢瓶留有5%气体空间作为安全系数,所以: 60℃〔1-5%〕1.2789=1.21kg/L〔充填系数〕 求做: 〔1〕0.5T的液氯钢瓶正常充装在0℃时充装500kg,温度上升到40℃时瓶气、液各占多少,在什么温度下才能充满? 〔2〕超装10%时钢瓶压力上升多少? 钢瓶容积400升,充填系数1.21kg/L 0℃时比容0.69L/kg 40℃时比容0.74L/kg 60℃时比容0.78L/kg 70℃时比容0.80L/kg 80℃时比容0.83L/kg 计算:
钢瓶液体的充装量按温度600C设计要求不能充满,必须留有气体空间,才是最安全的状态举例:某药厂,从化工厂运回0.5吨液氯重瓶,超重50公斤,当日最高温度35 0C,中午12时,车停在药厂爆晒,14时,液氯钢瓶中部大身爆裂,造成重大损失 分析其原因如下: 1、该钢瓶超重是事故的直接原因化工厂灌装人违章操作 2、当日最高温度是350C,钢瓶在下爆晒,地面温度大大超过350C气温是造成事故的主要原因运输人违章停车,〔运输危险品车辆不许中途停车吃饭,或做其它工作〕必须安置好后方可离开 3、其它的次要原因 我们知道液氯钢瓶正常充装,随着环境温度的升高,瓶压力加大,但它的爆炸点是多少,需要多大的压力呢? 破坏试验如下:〔水压试验〕1、 将钢瓶直立注满水,开始用试压泵向钢瓶注水升压,至液氯工作压力18公斤没有变化继续升至正常试验压力30公斤完好无损2、 水压升至89公斤这是钢瓶的强度极限,开始变形,钢瓶大身涨肚子,这时立即泄压,还在弹性围,能够还原3、 继续升高,就不能还原超过了弹性极限至158公斤时,从钢瓶大身中部裂开一个大口子,钢瓶破坏连续做了两个钢瓶破坏性试验,基本一样,效果相同。
总结:钢瓶设计完全符合国标,部标安全系数适合我国各地区安全使用〔后附充装表〕500公斤气瓶液氯充装表温度℃充装量Kg容积L充装系数Kg/L0℃时液氯体积0℃时气体空间温度上升时液氯容积温度上升时气相空间气瓶充满液体后温度上升,压力增加值〔大气压〕L%L%L%L%正常充装05004151.2134583701740"""37089451160"""3909425670"""40096.5153.580"""41510000超装10%05501.32538091.5358540"""4161000050"""60"""超装20%06001.4510"""20"""第三章 氯气钢瓶的基本知识一、 气瓶的分类: 气瓶是贮运式受压容器,在结构和使用方面,有一些不同于固定式受压容器的特殊要求,为了区别,一般把容积不超过1000升〔常用的35-60升〕用来盛装压缩气体,液化气体溶解气体的瓶式容器叫做气瓶气瓶可做以下分类:1. 按所充装气体分:有压缩气体、液化气体、溶解气体之分2. 按结构分:有无缝、焊接之分3. 按材料分:有碳钢、锰钢、铬钼钢等黑色金属和铝合金,不锈钢等另有玻璃钢、塑料等非金属材料之分。
4. 按制造方法分:有冲压拉伸法、钢管旋压法、焊接成型之分5. 按设计压力分有高压〔300、200、150、125kg/cm2〕和中低压〔80、50、30、10 kg/cm2〕之分二、 气瓶的结构及各部用途:1、 无缝气瓶的典型结构:钢制无缝气瓶的端部有五种形态加工方法是:无缝钢管旋压收底入口,钢坏冲压拉伸瓶体为碳素钢或合金钢等制成瓶身为长筒型瓶口部为锥螺纹,用来装配瓶阀,凸形底装有筒状或四角状的底座底座应热装,严禁与瓶体焊接如图1所示:图〔1〕2、 各部用途 〔1〕瓶帽:瓶帽的用途是保护瓶阀免受损瓶帽可有用钢管,可锻铸铁或铸铁制造当瓶阀漏气或防爆膜〔保险堵〕破裂时为防止瓶帽受压瓶帽上有排气孔排气孔应对称,以避免气体由一侧排出时的反作用,使气瓶倾倒瓶帽如图2所示:图〔2〕L´DD3L每254m/m的螺扣数155Φ8980.5<+0.3>2011 〔2〕瓶阀门:瓶阀门的用途是包装和使用的流量控制器,是一个较关键部位在使用过程中应注意维护保养要保证做到〔A〕密合圈不准有沟缝及坑洼阀座要平正〔B〕升降杆方头改须方正丝扣完整〔C〕其它丝扣处要完整〔D〕绝对保证不漏气瓶阀门如图3所示:图〔3〕三、 焊接瓶的结构及各部用途1、 焊接气瓶与低压气瓶的制造方法和低压容器一样。
也是用薄钢板滚圆后焊接成筒身,然后两端再焊上冲压成的封头〔后附图5〕图5 钢瓶简图液氯钢瓶型号径Dmm壁厚Smm总长Lmm容积V公升试验压力Kgf/cm2最大充装氯量吨最高使用温度℃设计使用年限年水压气压LP600-0.5LP800-160080081018002000400800303020200.5160601212 因为带折边的凹形到底不便于加工,所以往往是两端都用凸头〔半球形、椭圆形〕而在封底外焊接一个圆形的坐圈气瓶的封头上则焊接上一节中心孔,带有螺纹的短管,以便装配瓶阀 液氯钢瓶规格见表:钢瓶型号容积L径Dmm筒长L2mm壁厚Smm总长Vmm自重Kg针形阀、材料及数量1吨8008001310102020400青铜2个〔瓶阀〕0.5吨4006001210818002302、 钢瓶筒体和封头采用普通低锰合金钢1.6MnR制造在无缝气瓶中已谈到瓶阀门,瓶帽保险堵〔易熔塞〕这里就不重复了在焊接瓶中,瓶阀门为两个青铜阀门,叁个易熔塞〔0.5T〕此外我们从图中看到钢瓶有两根壁管,壁管的作用是充液瓶放置使两阀门中心连线垂直地面,这样可在下阀门放出液体在上阀门可放出气体因气体比液体轻得多,从图中可见,充液后瓶中液面线。
若是超量充装,液面线没有了两个针形阀门中心连接线再垂直地面也没用了放出来全是液体了在使用时若壁管断裂可换上下方向四、 气瓶的检验 为了保证气瓶的安全使用,防止和减少事故的发生,在气瓶使用过程中还要做定期检验容包括:气瓶外观检查,部检查以及水压试验等 〔1〕外观检查和音响试验: 气瓶在经长期的使用过程中,受到搬运、装卸、贮存、码垛等外部负荷,不可避免地要受到撞击和外伤,甚至于有严重划痕、裂纹或明显的变形,这应根据硬伤情况,损坏程度来确定降级或报废 除用肉眼观察外,还可用一种经验的方法,敲打瓶壁的音响来帮助判断,是否有局部缺陷或裂纹其音响的好坏与振动波的振幅强弱有关一般用木榔头打击来识别槌击声响清朗而余音较长为良好槌击音响发混浊,余音较短则为不良,此类瓶往往有裂纹 〔2〕部检查和壁厚测定: 气瓶长期使用不但要受外部撞击的影响,还会受到盛装的气体介质的腐蚀腐蚀的程度随使用年限、气瓶材质和气体种类而异例如:液氯严重腐蚀时,会出现斑点、腐蚀和片状腐蚀、丝状腐蚀,甚至铁锈成片状的往下剥落 气瓶的壁厚测定:国已普遍使用超声波测厚仪来测厚度,用以鉴别厚偏差和腐蚀程度〔3〕水压试验: 气瓶在使用过程中,必须进行水压试验,充装腐蚀性气体按规定每二年检验一次,气瓶水压试验的目的主要是测定气瓶强度。
水压试验两种方法:测法和外测法现测法普遍采用,优点是操作简便,缺点是计算复杂,误差较大 外测法具有计算简单,误差较小的优点是今后发展方向 《气瓶安全监察规程》提出了,测法检验气瓶其示意图如下:水压试验时温度不低于5℃即可进行水压试验应为工作压力的1.5倍试验时应缓慢升压至最高工作压力时,检查接头处无渗漏如无渗漏现象继续升高为试验压力,并保持1-2分钟不落压,然后降压进行全面检查一般低压气瓶可免做残余变形检查 五、气瓶检验工序及注意事项 1、试压检验操作:1) 试压使用介质如:水温应保证在5℃以上,不允计低于此温度,并且需使用干净的自来水,循环水不得混用,如试压氯瓶用过的水加入氨瓶或其它钢瓶,都是不允许的2) 将被检测钢瓶排净余气,摘除一个丝堵,钢瓶直立开始注自来水〔必须将被测钢瓶,水注的十分满,不要留有空间〕3) 上紧注水孔丝堵,一定要带上劲,防止漏水;同时抓紧试压〔注水瓶一般当日应完成,禁止长时间浸泡〕 4) 连接好试压泵,卡贝应带上劲,防止漏水,试压导管应采用专用钢网耐压管5) 检查钢瓶阀,丝堵有无漏水现象,试压泵水是否加足,无误后开泵6) 试压泵表压,应是被检钢瓶工作压力的1.5倍,如液氯瓶工作压力18Kg,表压应该是30Kg。
7) 试压泵应专人监视,表压稳定在规定的位置,若卸压应认真查清原因,是否有漏水部位,钢瓶有无变形,稳压5分钟,无变化才可认定试压合格8) 先关上钢瓶阀,再卸水压,防止带有余氯的水返回试压泵,损坏试压泵9) 将钢瓶放倒,带水过磅,记录重量,检验容积与原钢瓶,钢印容积是否相符10) 卸下全部丝堵,瓶阀放水洗瓶,再加清水冲洗同时摇动钢瓶,尽量冲净杂质、铁锈,达到铁锈、碎渣全部冲出为止 2、钢瓶壁检查1) 水压试验过的钢瓶,应立即进行干燥采用方法,蒸汽方法,蒸汽法,或者采用太阳能干燥法2) 排净钢瓶部水后,钢瓶直立在亮足,平整水泥地面为宜,约12小时左右,将钢瓶放倒,晒瓶大身,同时可以推动,尽量使钢瓶全部都晒到3) 晒到钢瓶壁全部干燥为止,用安全电压灯泡从丝堵口处探入,从其它堵处检查壁,确保干燥后,进行下一步检修4) 为了保证钢瓶使用不出或少出问题,进一步清除钢瓶壁杂物很有必要,一般采用,空压机吹气,将铁锈粉尘从丝堵口处排出,此项工作比较脏,但是不可缺少的一部份,它可以保证瓶两根壁管畅通,吹气过程中肉眼可直观瓶阀处出气若发现有片状铁锈需要用铅丝从丝堵处捣碎再吹出吹净后的钢瓶,用安全电压灯泡检查,瓶壁应干净无杂物。
5) 钢瓶安装两只新阀门,丝堵经过检修除锈后,六方应完好才可安装,丝扣损坏的,六方不整的应报废,安装瓶阀和堵,应有安装人,检验人签字,确保安装万无一失,避免使用中出现漏气现象3、 试压钢印打法规定1) 大瓶打在保护圈上,在前一次试压钢印后,排列整齐,新瓶应先打,试压单位代号,然后再打钢印2) 小瓶打在瓶肩部,在前一次试压钢印后3) 先打代号,后打年月,已有这次试压年月的,打下一次应试压年月4) 钢印要清楚可见,钢印模糊不清或乱,应从打 4、安全注意事项1) 钢瓶试水压的压力为钢瓶设计1.5倍2) 要严格控制试验压力,切不可超压3) 与钢瓶压力卸为零时,方可卸下瓶阀和丝堵4) 试压记录必须认真填写,容要全5) 试压时,肉眼可观察到体胖变形,应报废6) 导管、阀门、堵、丝扣坏者,应报废7) 瓶阀门一定要上紧,与地面平衡,垂直,瓶阀杆一定关闭,丝堵一定要旋紧第四章 液氯的安全使用、保管、运输一、 安全使用、仓储保管1、经外单位充装之氯、氨瓶和水厂用完退库之氯氨瓶在入库时,应作详细检查〔包括外观检查,有无摔痕,色漆是否完好,有无硬滑伤钢瓶完好情况,钢瓶阀门有无损伤,升降杆是否拧坏、拧断,阀门是否漏气,应检测是否关严密,钢瓶帽是否齐全有效,钢瓶盛装重量〕,无问题后,才能入库。
2、准备出库的液氯,液氨瓶,无论是空瓶或满瓶,在搬运前应由仓库负责人保管人会同领料人或搬运负责人共同检查下列工作,如有问题,不能发放出库1) 瓶充装之氯氨量不符标准〔超装多出公差量〕2) 钢瓶阀门漏气不严密,阀门丝扣严重损坏3) 防震胶圈是否完好,有无断裂或不少胶圈4) 钢瓶保护帽是否能带好,是否带好5) 货签是否完好,填写齐全6) 钢瓶保护圈是否完好,有无摔伤不圆现象3、 由库房发出和各厂退回的氯氨瓶经共同检查后,并做好台帐记录4、 保管、存放钢瓶应做到以下标准1) 氯气钢瓶和氨气钢瓶应分别存放〔包括空瓶〕,氨、氯库周围10米以不得存放易燃物品或危险物,严格按照市府办[1992]6号文件执行,区分八大类危险品2) 氯瓶40Kg的应立放,并设有栏杆或支架加以固定,不能立放时可以卧放,但要固定,以防钢瓶因地面不平而滚动,头部要朝一个方向,便于检修,通道不易太小3) 空瓶和满瓶应分别存放,码放要整齐,空瓶码放不许高于4层,重瓶必须单层码放4) 库房应安装排风设备,氯库房排风设备装窗子台下部位,易于排出氯气,氨库房排风设备装窗台以上,主要考虑氯气比空气重,氨气比空气轻所定5) 钢瓶安全帽必须旋紧。
5、严格执行氯、氨瓶先入库先发放使用的原则〔各厂氯氨瓶入库后15天如钢瓶阀开不动,由氯库负责退换〕认真填写有关记录〔包括钢瓶卡片〕 二、运输,有关法规、规定、标准、规则 1、1992年2月2日市人民政府办公厅转发了市交通局,市消防局,市公安交通管理局,市劳动局《关于整顿化学危险货物运输秩序加强安全管理的意见》,即京政办发[1992]6号文件,文件中明确由市交通局组成联合办公机构,对全市公路化学危险货物运输秩序进行整顿 2、根据京政办发[1992]6号文件精神,交通局于1992年5月21日发出了《关于加强公路化学危险货物运输组织管理的通知》,即京交运调字236号文件,文件中规定: 〔1〕成立公路化学危险货物运输调度中心,负责全市公路化学危险货特运输的组织管理、调度、平衡与协调工作〔2〕建立由运输组织管理办公室,定点代理站,营业性和非营业性运输单位组成的全市公路化学危险货物运输分工的原则3、1992年7月13日市消防局,公安交通管理局联合发布了《加强本市化学危险物品运输安全的通告》,通告中对从事化学危险物品运输的车辆、驾驶员、押运员的资格和技术标准提出了明确的要求,对运输危险物品车辆的行驶路线,停车场地也做出了明确的规定。
4、在交运管危字〔92〕和第18号《市公路化学危险货物非营业性运输,运输经营及运输代理经营条件》中,对从事公路化学危险货物非营业性运输条件,从事公路化学危险货物运输经营条件和从事公路化学危险货物运输代理经营条件做出了明确的规定5、 公路化学危险货物运输主要遵循的规则和技术标准有: 〔1〕交通部部标准JT3130-88《汽车危险货物运输规则》 〔2〕交通部部标准JT3145-91《汽车危险货物运输,装饰作业规程》 〔3〕交通部依据国家标准GB12268组织编写的《汽车运输危险货物品名表》〔人民交通1992年5月版〕 三、保管与运输1、 从事液氯工作的操作人员,仓库保管人员和运输人员,必须进行专业技术教育和定期考核,掌握一定安全知识,并严格遵守有关气瓶安全管理的规章制度,司机,装卸人员,仓库保管员都要持此上岗,并接受检查2、 对于盛装液氯的钢瓶,应建立钢瓶的技术档案,档案容如下: 记载钢瓶生产厂、钢瓶原始号、自重、容积、出厂日期等,技术卡片包括:工作压力、检验日期、外观检查结果、水压试验结果3、 氯库对于钢瓶的大修,小修〔包括定期防腐上漆,技术检验和充装液氯工作,要制订相就的系统安全操作规程。
4、 应有不同型号的防毒面具,备用滤毒罐各2个,并分别存放,防毒面具使用前应进行检查,无问题后才能配戴,配戴防毒面具时应注意的事项1) 防毒面具要定点悬挂储存,不要乱扔乱放2) 平时应练习配戴防毒面具,以达到熟练程度3) 药罐式防毒面具,使用时戴好后试验是否漏气,脸部与面具应严密,接口部位拧紧,用手堵住药罐底口,应憋气,呼吸基本正常后,才可正式操作,药罐式面具,药罐连续使用40分钟应报废更新4) 长管呼吸面具,使用的气源为空气,使用前查看表压,瓶贮存压力一般应在12-15Mpa,证明供气管系高压气密良好 试用呼吸面具时,手按面具下面的白色铝片,听到气源已有,再戴上面具,深呼吸数次,感觉正常舒畅,方可正式开始工作,当压力降至0.4Mpa时停止使用,更换气瓶 需要注意的:拔开快速接头时,应先放气,再拔开5) 必须齐备的工具: 胶皮手套A. 大绳、木杠、木楔B. 搬运超重设备C. 备用材料、零件,如鸡毛绳、铅皮、棉丝、钢丝刷等D. 使用的工具,克丝钳、活搬手、300mm、150mm或专用工具6) 运输中,应有一名能熟练掌握搬运规程和能排除故障的人负责指导运输工作,备好防护用品,备齐救援工具、材料。
7) 地区〔六月一日至八月三十日〕每日十时至十八时禁止运输四、漏气、漏液瓶紧急处理1. 发生跑氯时,切不可惊慌,否则呼吸急促,容易中毒,不可用鼻子寻找漏气处所,应用试液进行检查2. 严禁漏气瓶乱运,应采取措施,先将瓶〔小瓶立放,大瓶让瓶漏气口朝上,尽量。